Circuit Breaker Load Calculator

Safe continuous watts for any breaker at 120 or 240 volts.

Home and DIYUpdated 2026-10-112 min read
Circuit Breaker Load Calculator
Continuous amps
...
Continuous watts...
Wire pairing...

What it does

Breakers protect wires, not gadgets, and continuous loads get only 80% of the handle rating. A 20 A bedroom circuit therefore carries 16 A all evening, which is 1,920 W at 120 V, while short bursts may use the full 20.

The tool above takes breaker size with voltage. It returns continuous amps and watts with the typical copper wire beside it. The default 20 A at 120 V gives 16 A continuous (1,920 W) on 12 AWG.

Rules follow National Electrical Code practice through federal energy references: volts times amps is watts, continuous means 3 hours or more, and feeders size at 100% of the rest plus 125% of the continuous share. Energy Star panel guidance frames the same 120 versus 240 V upgrade choices.

Inverse sizing runs the math backward for new loads. A 32 A continuous EV charger needs 40 A of breaker, and a 1,500 W heater fits a 20 A 120 V circuit with room to spare.

How to use

  1. Pick the breaker handle size.
  2. Pick 120 or 240 volts.
  3. Read continuous amps first, watts beside it.
  4. Keep steady loads under the continuous line.
  5. Pair the listed copper wire before derates.
  6. Confirm panel capacity with an electrician.

Formula

Continuous amps = breaker x 0.8. Watts = breaker x volts x 0.8. Size up: breaker = continuous amps x 1.25.
0.8
NEC continuous load share of rating.
1.25
Inverse sizing factor for new continuous loads.
wire
Typical copper pairing before temperature derates.

Continuous means 3 hours or more at max current. Motors and inductive loads need power factor math beyond this page.

Worked example

Example: 20 A at 120 V

Defaults: 20 A breaker, 120 V.

  1. Amps: 20 x 0.8 = 16 A continuous.
  2. Watts: 20 x 120 x 0.8 = 1,920 W.
  3. Wire: 12 AWG copper typical.
  4. Heater check: 1,500 W fits under 1,920.
  5. 2,000 W continuous would need 20.83 A, so a 25 A circuit.
  6. Tool shows 16 A, 1,920 W, 12 AWG.

Reference table

Continuous capacity by circuit
CircuitContinuousWire typical
15 A x 120 V12 A, 1,440 W14 AWG
20 A x 120 V16 A, 1,920 W12 AWG
20 A x 240 V16 A, 3,840 W12 AWG
30 A x 240 V24 A, 5,760 W10 AWG
40 A x 240 V32 A, 7,680 W8 AWG
50 A x 240 V40 A, 9,600 W6 AWG

Limits

  • Single phase resistive math; motors differ.
  • Typical wire before derates and long runs.
  • Panel total capacity separate from branch math.
  • Local NEC edition and inspector rule.

Common mistakes

  • Loading 20 A continuous on a 20 A breaker.
  • Sizing wire to the load instead of the breaker.
  • Forgetting the 3 hour continuous definition.
  • Mixing 120 and 240 V in one product.
  • Backstabbing instead of proper terminations.

Try it yourself

Quick checks. Answers sit tucked under each question.

15 A at 120 V?

12 A continuous, 1,440 W, 14 AWG.

50 A at 240 V?

40 A continuous, 9,600 W, 6 AWG.

32 A continuous charger?

32 x 1.25 = 40 A breaker minimum.

Questions

Default capacity?

16 A (1,920 W) continuous on 20 A at 120 V.

Why 80%?

NEC continuous rule: heat builds over 3 plus hours.

30 A dryer at 240 V?

24 A (5,760 W) continuous on 10 AWG.

Wire pairing?

Typical copper before derates; confirm locally.

240 V effect?

Doubles watts per amp against 120 V.

Panel full?

Branch math passes but the service total still rules; ask an electrician.